To convert kW to amps on a single-phase circuit, multiply kilowatts by 1,000 and divide by volts: 10 kW at 240 V = 41.7 amps. Three-phase circuits split the load across three wires, so you also divide by 1.732 (the square root of 3). The calculator handles both directions, with a power factor for motors.
Convert kW and amps
kW to amps formulas
- Single-phase AC: amps = kW × 1,000 ÷ (volts × PF)
- Three-phase AC: amps = kW × 1,000 ÷ (1.732 × volts × PF), using line-to-line voltage
- DC: amps = kW × 1,000 ÷ volts
The reverse, amps to kW: single-phase kW = amps × volts × PF ÷ 1,000; three-phase kW = 1.732 × amps × volts × PF ÷ 1,000.
kVA vs kW. kVA (kilovolt-amps) is "apparent power", volts × amps without the power factor. Generators, transformers, and UPS units are often rated in kVA. kW = kVA × power factor, so a 10 kVA generator at a power factor of 0.8 delivers 8 kW. With a power factor of 1, the two are equal.
kW to amps chart: single-phase
U.S. homes use single-phase power at 120 and 240 volts. Power factor 1.
| kW | Amps at 120 V | Amps at 240 V |
|---|---|---|
| 1 kW | 8.3 | 4.2 |
| 2 kW | 16.7 | 8.3 |
| 3 kW | 25 | 12.5 |
| 5 kW | 41.7 | 20.8 |
| 7.2 kW | 60 | 30 |
| 10 kW | 83.3 | 41.7 |
| 11 kW | 91.7 | 45.8 |
| 15 kW | 125 | 62.5 |
| 20 kW | 166.7 | 83.3 |
| 25 kW | 208.3 | 104.2 |
| 30 kW | 250 | 125 |
kW to amps chart: three-phase
Three-phase power is used by businesses, apartment buildings, and large equipment: 208 V and 480 V in the U.S., 400 V in Europe and much of the world. Amps per phase, power factor 1.
| kW | 208 V | 400 V | 480 V |
|---|---|---|---|
| 1 kW | 2.8 | 1.4 | 1.2 |
| 5 kW | 13.9 | 7.2 | 6.0 |
| 10 kW | 27.8 | 14.4 | 12.0 |
| 11 kW | 30.5 | 15.9 | 13.2 |
| 15 kW | 41.6 | 21.7 | 18.0 |
| 20 kW | 55.5 | 28.9 | 24.1 |
| 30 kW | 83.3 | 43.3 | 36.1 |
| 50 kW | 138.8 | 72.2 | 60.1 |
| 100 kW | 277.6 | 144.3 | 120.3 |
Amps to kW chart
| Amps | 120 V 1-ph | 240 V 1-ph | 208 V 3-ph | 480 V 3-ph |
|---|---|---|---|---|
| 10 A | 1.2 kW | 2.4 kW | 3.6 kW | 8.3 kW |
| 15 A | 1.8 kW | 3.6 kW | 5.4 kW | 12.5 kW |
| 20 A | 2.4 kW | 4.8 kW | 7.2 kW | 16.6 kW |
| 30 A | 3.6 kW | 7.2 kW | 10.8 kW | 24.9 kW |
| 40 A | 4.8 kW | 9.6 kW | 14.4 kW | 33.3 kW |
| 50 A | 6.0 kW | 12.0 kW | 18.0 kW | 41.6 kW |
| 100 A | 12.0 kW | 24.0 kW | 36.0 kW | 83.1 kW |
| 200 A | 24.0 kW | 48.0 kW | 72.1 kW | 166.3 kW |
Power factor 1. Three-phase values use 1.732 × line-to-line voltage.
EV chargers: 7.2 kW, 11 kW, and 11.5 kW in amps
Level 2 home EV chargers are the most common reason people convert kW to amps. In the U.S., a charger drawing 30 amps at 240 volts delivers 7.2 kW, and one drawing 48 amps delivers 11.5 kW. Because charging is a continuous load, the circuit has to be rated at 125% of the charger's current: a 40-amp breaker for a 32-amp charger, and a 60-amp breaker for a 48-amp charger. In Europe, 11 kW chargers usually run on 400-volt three-phase power at 16 amps per phase.
A 200-amp home service at 240 volts can carry 48 kW in total, which is why large chargers sometimes need a load calculation by an electrician first. For the difference between kW and kWh when charging, see kW vs kWh.
Common questions
How do you convert kW to amps?
Single-phase: kW × 1,000 ÷ volts (÷ PF). Three-phase: kW × 1,000 ÷ (1.732 × volts × PF). 10 kW at 240 V is 41.7 A.
How many amps is 11 kW?
45.8 A at 240 V single-phase; 15.9 A per phase at 400 V three-phase.
How do you convert amps to kW?
Amps × volts × PF ÷ 1,000 (single-phase); × 1.732 for three-phase. 10 A at 240 V is 2.4 kW.
How many amps is 1 kW three-phase?
2.8 A at 208 V, 1.4 A at 400 V, 1.2 A at 480 V.
How many kW is 10 amps?
1.2 kW at 120 V, 2.4 kW at 240 V, single-phase.
Notes
- Formulas: standard power relations for DC, single-phase, and balanced three-phase AC circuits.
- 125% sizing for EV charging circuits follows the National Electrical Code's treatment of EV charging as a continuous load; an electrician confirms the requirements for your home.
Related converters: watts to amps, watts to kilowatts, and kW to MW.